Verasys

Johnson Controls Verasys

Описание линейки на русском языке внизу под товарами.

Johnson Controls Verasys ACC-PWRKIT-1E24
Johnson Controls Verasys ACC-WIFIKIT-0DU
Johnson Controls Verasys LC-SBH200-0
Johnson Controls Verasys LC-VAC1000-0
Johnson Controls Verasys LC-VAC1100-0
Johnson Controls Verasys LC-VAC3000-0
Johnson Controls Verasys PK-IOM1711-0
Johnson Controls Verasys PK-IOM2711-2
Johnson Controls Verasys PK-IOM2721-0
Johnson Controls Verasys PK-IOM3711-2
Johnson Controls Verasys PK-IOM3721-0
Johnson Controls Verasys PK-IOM3731-0
Johnson Controls Verasys PK-IOM4711-0
Johnson Controls Verasys PK-IOM5711-0
Johnson Controls Verasys PK-IOM5731-0
Johnson Controls Verasys PK-KIT1810-0
Johnson Controls Verasys PK-KIT1811-0
Johnson Controls Verasys PK-KIT3210-0
Johnson Controls Verasys PK-OEM1810-0
Johnson Controls Verasys PK-OEM1811-0
Johnson Controls Verasys PK-OEM1820-0
Johnson Controls Verasys PK-OEM1821-0
Johnson Controls Verasys PK-OEM3210-0
Johnson Controls Verasys PK-OEM3220-0
Johnson Controls Verasys TEC3610-00-000
Johnson Controls Verasys TEC3611-00-000
Johnson Controls Verasys TEC3612-00-000
Johnson Controls Verasys TEC3613-00-000
Johnson Controls Verasys TEC3620-00-000
Johnson Controls Verasys TEC3621-00-000
Johnson Controls Verasys TEC3622-00-000
Johnson Controls Verasys TEC3623-00-000
Johnson Controls Verasys TEC3630-00-000
Johnson Controls Verasys TEC3631-00-000
Johnson Controls Verasys TUC0312-2

Verasys – новая система управления зданием (BMS), разработанная фирмой Johnson Controls.

Если Metasys в основном предназначалась для крупных объектов, то Verasys ориентирована на небольшие коммерческие объекты типа офисов, магазинов, ресторанов, объекты торговли, клиники, супермаркеты и другие, площадью от 5000 кв. м до 9200 кв. м.

Verasys базируется на том же оборудовании (датчики, исполнительные устройства), что и Metasys, но в качестве контроллеров используются специально разработанные под новую систему – PEAK18/32 и VAC1000/3000.

Контроллеры отличаются от линейки FEC/FAC наличием стандартной библиотеки приложений (вентиляция, ИТП, бойлеры, управление освещением, контуры отопления), возможностью программирования с использованием USB накопителя и поддержкой протокола Modbus.

В Verasys для осуществления централизованного управления инженерным оборудованием не требуется разработка программного обеспечения для каждого контроллера (есть стандартная база), нет необходимости покупать, устанавливать, настраивать дорогостоящий сетевой управляющий контроллер (NIE/NAE/NCE), покупать и настраивать компьютер для установки сервера отображения, хранения и управления инженерным оборудованием здания (ADS/ADX).

Теперь для мониторинга и управления инженерным оборудованием требуется приобрести только одно устройство - специальный хаб SBH200.

При средней стоимости развертывания системы Metasys на базе NCE2510 и ADSLE5U от 500 т.р. (взята розничная стоимость оборудования, программного обеспечения и компьютера, без учета стоимости работ по установке, программированию, настройке), хаб SBH200 стоит в 4 раза дешевле и при этом не нужны работы по программированию и настройке сетевого контроллера и сервера ADS, что серьезно сокращает сроки введения в эксплуатацию системы Verasys.

Хаб SBH200:

- имеет встроенный web сервер с интуитивным интерфейсом пользователя;

- web интерфейс на HTML5, автоматически адаптируется к любому браузеру на любом устройстве (ПК, телефон, планшет);

- точка доступа Wi-Fi на USB адаптере позволяет быстро подключиться к системе даже при отсутствии локальной сети;

- ethernet порт (HTTPS, BACnetIP);

- Plug-and-Play со всеми компонентами системы Verasys, а так же Smart Equipment (чиллеры, бойлеры, фанкойлы и др.)

Возможности интерфейса SBH200:

- автоматическое формирование web интерфейса для различных применений и устройств;

- глобальная логика и расписания;

- архивирование/восстановление;

- тревоги(E-mail);

 

Для максимального сокращения времени развертывания Verasys необходимо использовать стандартные приложения. Описание и схемы подключения для различных инженерных систем Вы можете найти на нашем сайте и отправить нам запрос.

Разработчики Verasys оставили возможность создания специальных (не стандартных) приложений под требования Заказчика.

Не стандартное решение позволяет получить Заказчику то, что он желает, но при этом увеличивается стоимость системы, за счет разработки специализированного приложения, на 50% и увеличивается время внедрения системы на 5-30 дней в зависимости от количества требований к приложению.

Специалисты ООО «Центр управления» готовы предоставить Заказчику и проектировщикам АСУТП необходимую документацию и помощь.

Опросный лист для подбора оборудования Verasys.

 

Приточно-вытяжная установка без рекуперации

 

 

 

Controller

Point Type

Object Name

Expanded ID

Field Device

Signal

LC-VAC3000-0

BI IN1

SA-SD*

Supply Air Smoke Detector

Control Panel

Dry Contact

LC-VAC3000-0

BI IN2

LT-A

Freeze Stat Alarm

Control Panel

Dry Contact

LC-VAC3000-0

BI IN3

SF-S

Supply Fan Status

Current Relay

Dry Contact

LC-VAC3000-0

BI IN4

EF-S*

Exhaust Fan Status

Current Relay

Dry Contact

LC-VAC3000-0

BI IN5

DAPHI-A

Discharge Air Pressure High Alarm

P233A-10-PKC

Dry Contact

LC-VAC3000-0

BI IN6

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN7

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN8

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN9

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN10

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN11

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN12

Spare

Spare

Spare

Spare

LC-VAC3000-0

UI IN13

OA-T*

Outside Air Temperature

TS-6340E-000

10K NTC Thermistor

LC-VAC3000-0

UI IN14

DA-T

Supply Air Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN15

HWL-T*

Hot Water Coil Leaving Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN16

AHUFILT-S

Filter Status

Control Panel

Dry Contact

LC-VAC3000-0

UI IN17

HP-A*

Heating Coil Pump Alarm

Control Panel

Dry Contact

LC-VAC3000-0

UI IN18

DA-P

Supply Air Static Pressure

DP2500-R8-D

0-10 VDC

LC-VAC3000-0

CO OUT1

CLG-O*

Cooling Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT2

HTG-O*

Heating Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT3

SF-O

Supply Fan Output

SF VFD

0-10VDC

LC-VAC3000-0

CO OUT4

EF-O*

Exhaust Fan Output

EF VFD

0-10VDC

LC-VAC3000-0

AO OUT5

Spare

Spare

Spare

Spare

LC-VAC3000-0

RO OUT6

SF-C

Supply Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT7

EF-C*

Exhaust Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT8

HTG-C/HTG-STG1-C*

Heating Enable Command/Heating Stage 1 Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT9

HTG-STG2-C*

Heating Stage 2 Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT10

HP-C*

Heating Coil Pump Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT11

OAD-C*

Outdoor Air Damper Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT12

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT13

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT14

Spare

Spare

Spare

Spare

LC-VAC3000-0

SA Bus

ZN-T* / EA-T*

Zone Temperature with WC-Adj.

Exhaust Air Temperature Sensor

NS-ATF7002-0

NS-DTN7043-0

SAB (add: 199)

SAB (add: 204)

 

Приточно-вытяжная установка с рекуперацией

Controller

Point Type

Object Name

Expanded ID

Field Device

Signal

LC-VAC3000-0

BI IN1

SA-SD*

Supply Air Smoke Detector

Control Panel

Dry Contact

LC-VAC3000-0

BI IN2

LT-A

Freeze Stat Alarm

Control Panel

Dry Contact

LC-VAC3000-0

BI IN3

SF-S

Supply Fan Status

From Starter Panel

Dry Contact

LC-VAC3000-0

BI IN4

EF-S*

Exhaust Fan Status

From Starter Panel

Dry Contact

LC-VAC3000-0

BI IN5

HP-A*

Heating Coil Pump Alarm

Control Panel

Dry Contact

LC-VAC3000-0

BI IN6

HRW-S*

Heat Recovery Wheel Status

Control Panel

Dry Contact

LC-VAC3000-0

BI IN7

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN8

AHUFILT-S

Filter Status

Control Panel

24 VAC Detect

LC-VAC3000-0

BI IN9

EAFILT-S

Exhaust Air Filter Status

Control Panel

24 VAC Detect

LC-VAC3000-0

BI IN10

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN11

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN12

Spare

Spare

Spare

Spare

LC-VAC3000-0

UI IN13

OA-T

Outside Air Temperature

TS-6340E-000

10K NTC Thermistor

LC-VAC3000-0

UI IN14

EA-T

Exhaust Air Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN15

EAHR-T / GLY-T

Exhaust Air Heat Recovery Temperature / Glycol Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN16

DA-T

Supply Air Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN17

HWL-T*

Heating Coil Leaving Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN18

DA-P

Supply Air Static Pressure

DP2500-R8-D

0-10 VDC

LC-VAC3000-0

RO OUT6

SF-C

Supply Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT7

EF-C*

Exhaust Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT8

HTG-C / HTG-STG1-C*

Heating Enable Command / Heating Stage 1 Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT9

HTG-STG2-C / HP-C*

Heating Stage 2 Command/ Heating Coil Pump Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT10

HRW-C / HRP-C*

Heat Recovery Wheel Command/ Glycol Pump Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT11

OAD-C*

Outdoor Air Damper Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT12

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT13

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT14

Spare

Spare

Spare

Spare

LC-VAC3000-0

CO OUT1

CLG-O

Cooling Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT2

HTG-O*

Heating Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT3

HRW-O / HRV-O / HROAFBD-O*

Heat Recovery Wheel Output / Glycol Valve Output / Heat Recovery OA FBD Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT4

EF-O*

Exhaust Fan Output

VGxxxx

0-10VDC

LC-VAC3000-0

AO OUT5

 

Spare

Spare

 

LC-VAC3000-0

SA Bus

ZN-T*

Zone Temperature with WC-Adj.

NS-ATF7002-0

SAB (add: 199)

PK-IOM4711-4

UI IN1

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN2

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN3

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN4

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN5

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN6

Spare

Spare

Spare

Spare

PK-IOM4711-4

BI IN7

DAPHI-A

Discharge Air Pressure High Alarm

P233A-10-PKC

Dry Contact

PK-IOM4711-4

BI IN8

HRP-A*

Glycol Pump Alarm

Control Panel

Dry Contact

PK-IOM4711-4

BO OUT1

Spare

Spare

Spare

Spare

PK-IOM4711-4

BO OUT2

Spare

Spare

Spare

Spare

PK-IOM4711-4

BO OUT3

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT4

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT5

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT6

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT7

Spare

Spare

Spare

Spare

PK-IOM4711-4

AO OUT8

SF-O

Supply Fan Output

VGxxxx

0-10VDC

PK-IOM4711-4

AO OUT9

Spare

Spare

Spare

Spare