Verasys

Johnson Controls Verasys

Описание линейки на русском языке внизу под товарами.

Johnson Controls Verasys ACC-PWRKIT-1E24
Johnson Controls Verasys ACC-WIFIKIT-0DU
Johnson Controls Verasys LC-SBH200-0
Johnson Controls Verasys LC-VAC1000-0
Johnson Controls Verasys LC-VAC1100-0
Johnson Controls Verasys LC-VAC3000-0
Johnson Controls Verasys PK-IOM1711-0
Johnson Controls Verasys PK-IOM2711-2
Johnson Controls Verasys PK-IOM2721-0
Johnson Controls Verasys PK-IOM3711-2
Johnson Controls Verasys PK-IOM3721-0
Johnson Controls Verasys PK-IOM3731-0
Johnson Controls Verasys PK-IOM4711-0
Johnson Controls Verasys PK-IOM5711-0
Johnson Controls Verasys PK-IOM5731-0
Johnson Controls Verasys PK-KIT1810-0
Johnson Controls Verasys PK-KIT1811-0
Johnson Controls Verasys PK-KIT3210-0
Johnson Controls Verasys TEC3610-00-000
Johnson Controls Verasys TEC3611-00-000
Johnson Controls Verasys TEC3612-00-000
Johnson Controls Verasys TEC3613-00-000
Johnson Controls Verasys TEC3620-00-000
Johnson Controls Verasys TEC3621-00-000
Johnson Controls Verasys TEC3622-00-000
Johnson Controls Verasys TEC3623-00-000
Johnson Controls Verasys TEC3630-00-000
Johnson Controls Verasys TEC3631-00-000
Johnson Controls Verasys TUC0312-2

Verasys – новая система управления зданием (BMS), разработанная фирмой Johnson Controls.

Если Metasys в основном предназначалась для крупных объектов, то Verasys ориентирована на небольшие и средние объекты (офисов, магазинов, ресторанов, объекты торговли, клиники, супермаркеты и другие).

Verasys базируется на том же оборудовании (датчики, исполнительные устройства), что и Metasys, но в качестве контроллеров используются специально разработанные под новую систему – PEAK18/32 и VAC1000/3000.

Контроллеры отличаются от линейки FEC/FAC наличием стандартной библиотеки приложений (вентиляция, ИТП, бойлеры, управление освещением, контуры отопления), возможностью программирования с использованием USB накопителя и поддержкой протокола Modbus.

В Verasys для осуществления централизованного управления инженерным оборудованием не требуется разработка программного обеспечения для каждого контроллера (есть стандартная база), нет необходимости покупать, устанавливать, настраивать дорогостоящий сетевой управляющий контроллер (NIE/NAE/NCE), покупать и настраивать компьютер для установки сервера отображения, хранения и управления инженерным оборудованием здания (ADS/ADX).

Теперь для мониторинга и управления инженерным оборудованием требуется приобрести только одно устройство - специальный хаб SBH200.

При средней стоимости развертывания системы Metasys на базе NCE2510 и ADSLE5U от 500 т.р. (взята розничная стоимость оборудования, программного обеспечения и компьютера, без учета стоимости работ по установке, программированию, настройке), хаб SBH200 стоит в 4 раза дешевле и при этом не нужны работы по программированию и настройке сетевого контроллера и сервера ADS, что серьезно сокращает сроки введения в эксплуатацию системы Verasys.

Хаб SBH200:

- имеет встроенный web сервер с интуитивным интерфейсом пользователя;

- web интерфейс на HTML5, автоматически адаптируется к любому браузеру на любом устройстве (ПК, телефон, планшет);

- точка доступа Wi-Fi на USB адаптере позволяет быстро подключиться к системе даже при отсутствии локальной сети;

- ethernet порт (HTTPS, BACnetIP);

- Plug-and-Play со всеми компонентами системы Verasys, а так же Smart Equipment (чиллеры, бойлеры, фанкойлы и др.)

Возможности интерфейса SBH200:

- автоматическое формирование web интерфейса для различных применений и устройств;

- глобальная логика и расписания;

- архивирование/восстановление;

- тревоги(E-mail);

 

Для максимального сокращения времени развертывания Verasys необходимо использовать стандартные приложения. Описание и схемы подключения для различных инженерных систем Вы можете найти на нашем сайте и отправить нам запрос.

Разработчики Verasys оставили возможность создания специальных (не стандартных) приложений под требования Заказчика.

Специалисты ООО «Центр управления» готовы предоставить Заказчику и проектировщикам АСУТП необходимую документацию и помощь.

Опросный лист для подбора оборудования Verasys.

 

Приточно-вытяжная установка без рекуперации

 

 

 

Controller

Point Type

Object Name

Expanded ID

Field Device

Signal

LC-VAC3000-0

BI IN1

SA-SD*

Supply Air Smoke Detector

Control Panel

Dry Contact

LC-VAC3000-0

BI IN2

LT-A

Freeze Stat Alarm

Control Panel

Dry Contact

LC-VAC3000-0

BI IN3

SF-S

Supply Fan Status

Current Relay

Dry Contact

LC-VAC3000-0

BI IN4

EF-S*

Exhaust Fan Status

Current Relay

Dry Contact

LC-VAC3000-0

BI IN5

DAPHI-A

Discharge Air Pressure High Alarm

P233A-10-PKC

Dry Contact

LC-VAC3000-0

BI IN6

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN7

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN8

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN9

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN10

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN11

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN12

Spare

Spare

Spare

Spare

LC-VAC3000-0

UI IN13

OA-T*

Outside Air Temperature

TS-6340E-000

10K NTC Thermistor

LC-VAC3000-0

UI IN14

DA-T

Supply Air Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN15

HWL-T*

Hot Water Coil Leaving Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN16

AHUFILT-S

Filter Status

Control Panel

Dry Contact

LC-VAC3000-0

UI IN17

HP-A*

Heating Coil Pump Alarm

Control Panel

Dry Contact

LC-VAC3000-0

UI IN18

DA-P

Supply Air Static Pressure

DP2500-R8-D

0-10 VDC

LC-VAC3000-0

CO OUT1

CLG-O*

Cooling Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT2

HTG-O*

Heating Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT3

SF-O

Supply Fan Output

SF VFD

0-10VDC

LC-VAC3000-0

CO OUT4

EF-O*

Exhaust Fan Output

EF VFD

0-10VDC

LC-VAC3000-0

AO OUT5

Spare

Spare

Spare

Spare

LC-VAC3000-0

RO OUT6

SF-C

Supply Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT7

EF-C*

Exhaust Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT8

HTG-C/HTG-STG1-C*

Heating Enable Command/Heating Stage 1 Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT9

HTG-STG2-C*

Heating Stage 2 Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT10

HP-C*

Heating Coil Pump Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT11

OAD-C*

Outdoor Air Damper Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT12

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT13

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT14

Spare

Spare

Spare

Spare

LC-VAC3000-0

SA Bus

ZN-T* / EA-T*

Zone Temperature with WC-Adj.

Exhaust Air Temperature Sensor

NS-ATF7002-0

NS-DTN7043-0

SAB (add: 199)

SAB (add: 204)

 

Приточно-вытяжная установка с рекуперацией

Controller

Point Type

Object Name

Expanded ID

Field Device

Signal

LC-VAC3000-0

BI IN1

SA-SD*

Supply Air Smoke Detector

Control Panel

Dry Contact

LC-VAC3000-0

BI IN2

LT-A

Freeze Stat Alarm

Control Panel

Dry Contact

LC-VAC3000-0

BI IN3

SF-S

Supply Fan Status

From Starter Panel

Dry Contact

LC-VAC3000-0

BI IN4

EF-S*

Exhaust Fan Status

From Starter Panel

Dry Contact

LC-VAC3000-0

BI IN5

HP-A*

Heating Coil Pump Alarm

Control Panel

Dry Contact

LC-VAC3000-0

BI IN6

HRW-S*

Heat Recovery Wheel Status

Control Panel

Dry Contact

LC-VAC3000-0

BI IN7

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN8

AHUFILT-S

Filter Status

Control Panel

24 VAC Detect

LC-VAC3000-0

BI IN9

EAFILT-S

Exhaust Air Filter Status

Control Panel

24 VAC Detect

LC-VAC3000-0

BI IN10

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN11

Spare

Spare

Spare

Spare

LC-VAC3000-0

BI IN12

Spare

Spare

Spare

Spare

LC-VAC3000-0

UI IN13

OA-T

Outside Air Temperature

TS-6340E-000

10K NTC Thermistor

LC-VAC3000-0

UI IN14

EA-T

Exhaust Air Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN15

EAHR-T / GLY-T

Exhaust Air Heat Recovery Temperature / Glycol Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN16

DA-T

Supply Air Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN17

HWL-T*

Heating Coil Leaving Temperature

TS-6340D-xxx

10K NTC Thermistor

LC-VAC3000-0

UI IN18

DA-P

Supply Air Static Pressure

DP2500-R8-D

0-10 VDC

LC-VAC3000-0

RO OUT6

SF-C

Supply Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT7

EF-C*

Exhaust Fan Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT8

HTG-C / HTG-STG1-C*

Heating Enable Command / Heating Stage 1 Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT9

HTG-STG2-C / HP-C*

Heating Stage 2 Command/ Heating Coil Pump Command

Relay

24 VAC Maintained

LC-VAC3000-0

RO OUT10

HRW-C / HRP-C*

Heat Recovery Wheel Command/ Glycol Pump Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT11

OAD-C*

Outdoor Air Damper Command

Relay

24 VAC Maintained

LC-VAC3000-0

BO OUT12

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT13

Spare

Spare

Spare

Spare

LC-VAC3000-0

BO OUT14

Spare

Spare

Spare

Spare

LC-VAC3000-0

CO OUT1

CLG-O

Cooling Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT2

HTG-O*

Heating Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT3

HRW-O / HRV-O / HROAFBD-O*

Heat Recovery Wheel Output / Glycol Valve Output / Heat Recovery OA FBD Output

VGxxxx

0-10VDC

LC-VAC3000-0

CO OUT4

EF-O*

Exhaust Fan Output

VGxxxx

0-10VDC

LC-VAC3000-0

AO OUT5

 

Spare

Spare

 

LC-VAC3000-0

SA Bus

ZN-T*

Zone Temperature with WC-Adj.

NS-ATF7002-0

SAB (add: 199)

PK-IOM4711-4

UI IN1

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN2

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN3

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN4

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN5

Spare

Spare

Spare

Spare

PK-IOM4711-4

UI IN6

Spare

Spare

Spare

Spare

PK-IOM4711-4

BI IN7

DAPHI-A

Discharge Air Pressure High Alarm

P233A-10-PKC

Dry Contact

PK-IOM4711-4

BI IN8

HRP-A*

Glycol Pump Alarm

Control Panel

Dry Contact

PK-IOM4711-4

BO OUT1

Spare

Spare

Spare

Spare

PK-IOM4711-4

BO OUT2

Spare

Spare

Spare

Spare

PK-IOM4711-4

BO OUT3

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT4

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT5

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT6

Spare

Spare

Spare

Spare

PK-IOM4711-4

CO OUT7

Spare

Spare

Spare

Spare

PK-IOM4711-4

AO OUT8

SF-O

Supply Fan Output

VGxxxx

0-10VDC

PK-IOM4711-4

AO OUT9

Spare

Spare

Spare

Spare